ASi gateway configuration

Double click on the “AC1422” gateway in the DTM browser window.

 

 

If you select the equipment, you get information on EDS of that equipment.

 

 

 

 

 

 

The tab: "Identity verification" allows you to add an identification strategy to verify that the equipment corresponds to that configured or to verify that it is compatible.

 

 

 

By clicking on: "Exclusive Owner", you can configure connection parameters :

-          The connection refresh period, in milliseconds

-          The size of the inputs / outputs

-          The input / output mode

-          The type of inputs / outputs

-          Input / output priorities

-          The input trigger

 

 

In the tab: "Configuration parameter" you can change the address extension of each ASI module that can be connected to the gateway.

An AC1422 gateway can receive: 

  • 2 x 31 digital inputs
  • 3 analog inputs on 16bit
  • 3 analog outputs on 16 bit